Designing container and modular houses for the Gaza Strip. This guide turns the site’s climate and solar geometry into construction-ready numbers. It is based on a full-year solar-position computation (NOAA algorithm, four key-date self-check error 0.000°) combined with the coastal, geological and climatic constraints of the Eastern Mediterranean coast.

Free technical report — download the full 23-page PDF
The complete study with all figures, derivation tables and the design parameter quick-reference is available as a PDF:

Download the Gaza Climate & Solar Design Guide (PDF, 23 pages)

Executive Summary — Five Key Findings

  1. The noon sun stays south of zenith all year — there is no shadow-reversal period. At 31.50°N the latitude always exceeds the solar declination (±23.4°), so on all 365 days the noon sun lies south of zenith. A single fixed south-side shading design works year-round — unlike tropical sites such as 18°N in the Caribbean, which have an ~80-day reversal period.
  2. Shade in summer, gain in winter. Noon altitude swings from 35.07° (winter solstice) to 81.96° (summer solstice) — an amplitude of 46.88°. Summer sun is almost vertical (needing only D/H = 0.14 of overhang) while winter temperatures are just 8–19 °C and winter sun is wanted. A shallow 0.5–0.6 m overhang is the optimum.
  3. South is the strongest exposed face. Annual heat-gain index: SW 37.26 ≈ SE 37.24 > S 35.15 > W 31.17 ≈ E 31.16 > NE/NW 14.65 > N 3.18. East and west receive sun at only 14–40° altitude, which would need D/H = 1.18–4.02 of overhang — geometrically impossible. Vertical fins are mandatory there.
  4. The roof is the number-one heat-load surface. Roof incidence cosine rises from 0.575 (winter) to 0.990 (summer solstice); June–August alone carry 30.1% of annual irradiation. It is also the best surface for PV, since winter noon altitude stays ≥35°.
  5. Success depends on salt spray, seismic liquefaction and dust — not on angles. These three coastal constraints must be handled at concept stage or they cannot be remedied cheaply later.

1. Climate & Geography

Gaza lies on the Eastern Mediterranean coast, a low-lying sandy coastal plain with shallow, saline groundwater and a high water table. It has a textbook Mediterranean climate: hot, dry, almost rainless summers and mild, wet winters.

Site parametersClimate values (1991–2020 mean)
Coordinates31.50°N, 34.47°EHottest monthJul–Aug, mean max 32 °C
TerrainSandy coastal plainColdest monthJan, mean min 8 °C
Prevailing windW / SW sea breezeAnnual rainfall300–400 mm
Special windSpring Khamsin (hot, dusty, S)Rain concentration~80% in Nov–Mar
Seismic settingDead Sea transform influence; sandy-soil liquefaction riskCoastal humidity60–75% RH
Gaza climate and solar geometry figure
Fig. 4 Monthly temperature and rainfall, Gaza. Rainfall and temperature are anti-phased: the wettest months (Dec–Jan) are also the coldest, and the hottest months (Jul–Aug) are virtually rainless. This is the physical basis on which summer shading, winter solar gain and concentrated wet-season drainage all hold at once.
⚠ Design priority
Gaza is a low-latitude subtropical site with severe coastal corrosion and moderate seismicity. Such projects almost never fail because a shading angle was imprecise — they fail because the envelope rusts through, the foundation settles differentially in an earthquake, and dust chokes the ventilation. Priority order: durability (corrosion / foundation) > ventilation & dust control > shading & solar gain > aesthetics.

2. Solar Geometry

Solar position is computed with the NOAA declination Fourier series and equation of time, with the solar transit time solved exactly for each day. The astronomical identity noon altitude = 90° − |latitude − declination| returns an error of 0.000° on all four key dates, so every angle and dimension below is fit for construction.

Key dateDeclinationNoon altitudeIdentity checkError
Spring Equinox−0.07°58.43°58.43°0.000°
Summer Solstice+23.45°81.95°81.95°0.000°
Autumn Equinox+0.25°58.75°58.75°0.000°
Winter Solstice−23.42°35.08°35.08°0.000°
Gaza climate and solar geometry figure
Fig. 2 Annual noon solar altitude (red) and declination (blue dashed). The grey dotted line is the site latitude, 31.5°. The blue declination curve stays below the grey latitude line all year — the graphical proof that the sun remains south of zenith with no reversal period.
OrientationAnnual heat-gain indexRelativeEngineering implication
South-west37.26100.0%Highest load; afternoon west sun
South-east37.2499.9%Effectively equal; morning east sun
South35.1594.3%Longest exposure; most efficient shading
West31.1783.7%Vertical shading required
East31.1683.6%Vertical shading required
North-west14.6539.3%Negligible summer evening sun
North-east14.6539.3%Negligible summer morning sun
North3.188.5%Suitable as primary daylight face
Gaza climate and solar geometry figure
Fig. 1 Annual sun-path polar diagram, Gaza. Radial axis = solar altitude; circumferential = azimuth from North. All four noon points fall on the southern half — consistent with the no-reversal-period finding.
★ A counter-intuitive but important effect
South-facade exposure at the equinoxes reaches 11.9 h/day — higher than the 6.0 h at the summer solstice. At the summer solstice the sun rises north-east and sets north-west, so the south facade is actually shaded in the early morning and late afternoon. South shading must be checked against the equinoxes, not only the summer solstice.
Gaza climate and solar geometry figure
Fig. 3 Annual heat-gain index by orientation (left) and seasonal sun exposure (right). The south facade is the only one with high exposure in every season.
Gaza climate and solar geometry figure
Fig. 5 Monthly share of horizontal (roof) irradiation. June–August together carry about 30.1% of annual irradiation — the primary heat-load period for the roof.

3. Design Recommendations

3.1 Shading: shallow south overhang + vertical fins east/west

Key dateNoon altitudeRequired D/HProjection for 1.5 m window
Summer Solstice81.95°0.1410.21 m
Spring Equinox58.43°0.6140.92 m
Autumn Equinox58.75°0.6070.91 m
Winter Solstice35.08°1.4242.14 m — need not be satisfied
★ Recommended: 0.50–0.60 m south-facing horizontal overhang

  • Summer (noon altitude >75°): shading depth ≈ 0.6 × tan(82°) ≈ 4.3 m ≫ window height → the south window is fully shaded.
  • Equinoxes (altitude ≈58.5°): shading depth ≈ 0.98 m, blocking 65% of a 1.5 m window → controls transition-season overheating.
  • Winter (altitude ≈35°): shading depth ≈ 0.42 m, blocking only 28% → 72% of winter sun penetrates indoors for passive heating.

The same 0.6 m overhang blocks tightly in summer and lets sun in during winter. Do not size it to the winter value (D/H = 1.424, 2.14 m) — that would block the valuable winter sun and is also impractical under coastal wind loading.

★ East/west: horizontal overhangs are geometrically useless. At 08:00/16:00 the sun altitude is only 14–40°, requiring D/H = 1.18–4.02 — impossible with a horizontal overhang. Use vertical fins (spacing ≈ fin depth × 1.0–1.3) or recess windows 0.3–0.5 m.

3.2 Roof, envelope and ventilation

  • Cool roof: high-reflectance coating (SRI ≥ 78) + a ventilated roof void to remove accumulated heat by natural convection.
  • Wall insulation: sandwich-panel core density ≥ 120 kg/m³, thickness 75–100 mm, Class A fire (rock wool preferred).
  • Corrosion protection (top priority): AZ150 aluminised-zinc or hot-dip galvanising ≥ 100 μm; 316 stainless fasteners; never allow dissimilar metals to touch.
  • Moisture control: place the vapour/water barrier on the outer side of the envelope; seal all panel joints.
  • Ventilation: closable + G3–G4 filtered dual-mode vents (summer cooling vs. Khamsin dust season); inlet on the south-west sea-breeze side.
  • Drainage: design roof slope and gutters to the local return-period storm; with 80% of rainfall concentrated in winter, leakage risk is high.

3.3 Foundations and liquefaction resistance

★ The foundation is the lifeline of structural safety

  • Liquefaction treatment: gravel / graded sand-gravel replacement with compaction, or isolated/strip footings with increased depth and width.
  • Anchoring: the seismic weak points are the unit-to-unit and unit-to-foundation connections — use high-strength corner-casting bolts/twist locks to tie all units and the foundation into one body.
  • Elevation: keep the underside of units at least 300 mm above grade, with under-floor ventilation.
  • Regular, symmetric layout: avoid large cantilevers and local projections to prevent torsional seismic effects.
  • Raise the platform: for a low-lying coastal site, raise the base plinth to counter winter storm ponding and sea-level-rise background.

4. Design Parameter Quick-Reference

Site31.50°N / 34.47°E; UTC+2 (UTC+3 DST approx. Apr–Oct)
North-of-zenith periodNone (noon sun south of zenith on all 365 days)
Noon altitude range35.07° (winter) – 81.96° (summer)
Primary shading orientationSouth (fixed; no two-sided shading needed); secondary SE/SW
Recommended daylight orientationNorth (index 3.18, 9% of south)
Building long axisEast–west
South overhang0.50–0.60 m (D/H ≈ 0.33–0.40): full shade in summer / 65% at equinoxes / 28% in winter
East/west shadingVertical fins, spacing ≈ depth × 1.0–1.3; or recess windows 0.3–0.5 m
RoofHigh-reflectance coating (SRI ≥ 78) + ventilated roof void
Wall insulationCore ≥ 120 kg/m³, 75–100 mm, Class A fire
Corrosion protectionAZ150 / hot-dip galvanising ≥ 100 μm; 316 stainless fasteners
FoundationsCompacted gravel replacement + strip/isolated footings; units ≥ 300 mm above grade; anchored
PhotovoltaicsViable year-round (winter noon altitude still ≥ 35°)

Download the Full Report

HUAYING — Gaza Strip Climate & Solar Geometry Design Guidance
23 pages, fully illustrated, with derivation tables, climate data and the complete design parameter quick-reference.

Download PDF (English, 23 pages)

Scope and limitations

  • The solar-geometry results apply to the whole Gaza Strip; climate figures are representative of the coastal plain.
  • Informative for other 23.5°–35°N subtropical Mediterranean coastal sites, but not directly applicable to tropical sites (which have a reversal period) or the southern hemisphere.
  • This study does not replace the structural calculations a local engineer must perform against the current seismic design intensity, basic wind pressure and ground snow load.
  • Corrosion category, coating service life and foundation liquefaction treatment should be finalised against the site geotechnical investigation.